Field Setting from Outdoor Unit
74
No.
Setting item
Setting of difference
35
in height for the
outdoor unit
Emergency
operation
(Setting for the
master unit
38
operation
prohibition in multi-
outdoor-unit
system)
Emergency
operation
(Setting for the
slave unit 1 and 2
39
operation
prohibition in multi-
outdoor-unit
system)
Emergency
operation
(Setting for the
slave unit 3
40
operation
prohibition in multi-
outdoor-unit
system)
Master-slave set-up
55
for multi outdoor
units
The numbers in the "No." column represent the number of times to press
the SET (BS2) button.
Description
Make the setting when the outdoor unit is installed 40 m
or more below the indoor unit.
Used to temporarily prohibit the applicable outdoor unit
from operating should there be any defective part in multi-
outdoor-unit system. Since the comfortable environment
is extremely impaired, prompt replacement of the part is
required.
Set up master and slave units for multi-connection
outdoor units.
After setting up, press the
seconds or more.
SiBE341027
BS5 (RESET)
button for 5
Test Operation