Address Duplication Of Centralized Controller - Daikin VRV II-Q RQYQ8-48PY1B Service Manual

R-410a 50hz heat pump
Table of Contents

Advertisement

Troubleshooting by Remote Controller

2.39 Address Duplication of Centralized Controller

UC
Remote
Controller
Display
Applicable
All models of indoor unit
Models
Centralized controller
Method of Error
The principal indoor unit detects the same address as that of its own on any other indoor unit.
Detection
Error Decision
The error decision is made as soon as the abnormality aforementioned is detected.
Conditions
Supposed
Causes
Troubleshooting
172

Address duplication of centralized controller

Defective the indoor unit PCB.
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
The centralized address is
duplicated.
SiBE341027
Make setting change so that
the centralized address will
not be duplicated.
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents