Daikin VRV II-Q RQYQ8-48PY1B Service Manual page 192

R-410a 50hz heat pump
Table of Contents

Advertisement

Troubleshooting by Remote Controller
CHECK 4
Power Transistor Check
Perform the following procedures prior to check.
(1) Power Off.
(2) Remove all the wiring connected to the PCB where power transistors are mounted on.
[Preparation]
· Tester
[Point of Measurement and Judgement Criteria]
· Measure the resistance value using a tester at each point of measurement below, 10 minutes later after power OFF.
To use analog tester:
Measurement in the resistance value mode in the range of
multiplying 1kΩ.
Point of Measurement
No.
+
1
P2
U
P2
V
2
3
P2
W
4
U
P2
V
P2
5
6
P2
W
7
U
N3
8
N3
V
9
N3
W
10
U
N3
11
V
N3
W
12
N3
[PCB and Circuit Diagram]
182
Judgement Criteria
Remarks
2 ~ 15kΩ
Due to condenser charge
15kΩ and
and so on, resistance
above
measurement may require
(including )
some time.
2 ~ 15kΩ
∗ Preparing a tester in the analog system is recommended.
A tester in the digital system with diode check function will
be usable.
To use digital tester:
Measurement is executed in the diode check mode. (
Point of Measurement
No.
Judgement Criteria
+
1
P2
U
P2
V
1.2V and over
2
3
P2
W
4
U
P2
5
V
P2
6
P2
W
0.3 ~ 0.7V
U
7
N3
8
N3
V
N3
W
9
10
U
N3
11
1.2V and over
V
N3
W
12
N3
SiBE341027
)
Remarks
Due to condenser charge
and so on, resistance
measurement may require
some time.
Due to condenser charge
and so on, resistance
measurement may require
some time.
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents