2.25 Transmission System Error (between Inverter and Main
PCB)
LC
Remote
Controller
Display
Applicable
RQYQ-PY1B
Models
Method of Error
Check the communication state between inverter PCB and main PCB by micro-computer.
Detection
Error Decision
When the transmission is not carried out in a specified period of time or longer.
Conditions
Supposed
Causes
Service Diagnosis
Incorrect transmission wiring between the inverter PCB and outdoor unit main PCB
Defective outdoor unit main PCB (transmission section)
Defective inverter PCB
Defective noise filter
External factor (noise etc.)
Defective inverter compressor
Defective fan motor