Field Setting from Outdoor Unit
Set Cool / Heat for More Than One Outdoor Unit System Simultaneously in Accordance with Unified
Master Outdoor Unit by Cool / Heat Select Remote Controller
Install the external control adaptor for outdoor unit on either the outdoor-outdoor, indoor-outdoor
transmission line.
Mount the COOL/HEAT selector to the unified master outdoor unit.
Set the DS1-1 on the PCB of unified master outdoor unit to OUT.
In setting mode 1, set the outdoor unit you want to give cool/heat selection permission to as the unified
master, and set the other outdoor units as unified slave units.
When multiple external control adaptors for outdoor unit are used and cool / heat is selected for each
external control adaptor for outdoor unit, use "setting mode 2" and set DS1 and DS2 on the external
control adaptors for outdoor unit and the unified cool / heat address on the outdoor unit main PCB to the
same address No. (For details, refer to the following page.).
External control adaptor for outdoor unit
BOTH
FUNCTION
CENTRAL
C/H
NO.
<Master unit>
IND
OUT
IN
C/H SELECTOR
To indoor unit
Multi outdoor units connection
82
C/H SELECT
CENTRAL
IND
C/H
SELECTOR
OFF
ON
OUT
C/H
DE
IN
C/H SELECTOR
TERMINAL
ADDRESS
Cool/Heat
To indoor unit
selector
C/H SELECT
MASTER
SLAVE
C/H SELECT
OUT-MULTI
MASTER
SLAVE
C/H SELECT
OUT-MULTI
<Slave unit>
C/H SELECT
IND
MASTER
C/H SELECT
OUT
IN
C/H SELECTOR
C/H SELECT
IND
MASTER
C/H SELECT
OUT
IN
C/H SELECTOR
To indoor unit
SLAVE
OUT-MULTI
SiBE341027
SLAVE
OUT-MULTI