Compressor Pi Control - Daikin VRV II RXYQ5MY1B Service Manual

R-410a heat pump 50hz
Hide thumbs Also See for VRV II RXYQ5MY1B:
Table of Contents

Advertisement

SiE39-404
2.2

Compressor PI Control

Compressor PI Control

Carries out the compressor capacity PI control to maintain Te at constant during cooling
operation and Tc at constant during heating operation to ensure stable unit performance.
[Cooling operation]
Controls compressor capacity to adjust Te to
achieve target value (TeS).
Te setting
[Heating operation]
Controls compressor capacity to adjust Tc to
achieve target value (TcS).
Tc setting
Function
L
M (Normal)
H
(factory
setting)
3
6
9
L
M (Normal)
H
(factory
setting)
43
46
49
Te : Low pressure equivalent saturation temperature
(°C)
TeS : Target Te value
(Varies depending on Te setting, operating
frequency, etc.)
Tc : High pressure equivalent saturation temperature
(°C)
TcS : Target Tc value
(Varies depending on Tc setting, operating
frequency, etc.)
Basic Control
77

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents