Daikin VRV II-Q RQYQ8-48PY1B Service Manual page 83

R-410a 50hz heat pump
Table of Contents

Advertisement

SiBE341027
b. "Setting mode 2"
Press and hold the MODE (BS1)
button for 5 seconds and set to
"Setting mode 2".
<Selection of setting items>
Press the SET (BS2) button and set
the LED display to a setting item
shown in the table on the right.
Press the RETURN (BS3) button and
decide the item. (The present setting
condition is blinked.)
<Selection of setting conditions>
Press the SET (BS2) button and set
to the setting condition you want.
Press the RETURN (BS3) button and
decide the condition.
Press the RETURN (BS3) button and
set to the initial status of "Setting
mode 2".
∗ If you become unsure of how to
proceed, press the MODE (BS1)
button and return to setting mode 1.
Test Operation
No.
Setting item
Digital pressure
0
gauge kit display
Cool/heat unified
1
address
Low noise/demand
2
address
Test operation
3
settings
Indoor unit forced
5
fan H
Indoor unit forced
6
operation
8
Te setting
9
Tc setting
10 Defrost changeover
setting
11 Sequential
operation setting
External low noise
12
setting / Demand
setting
13 Setting of AIRNET
address
16 Setting of hot water Make this setting to conduct heating operation with hot
18 High static pressure
setting
19 Emergency
operation
Additional
20
refrigerant charging
operation setting
Refrigerant recovery/
21
vacuuming mode
setting
22 Low night noise
setting
25 Setting of external
low noise level
Low night noise
26
operation start
setting
Low night noise
27
operation end
setting
Power transistor
check mode
∗Check after
28
disconnection of
compressor wires
29 Capacity priority
setting
30 Demand setting 1
32 Normal demand
setting
Field Setting from Outdoor Unit
Description
Used to make setting of contents to display on the digital
pressure gauges (e.g. pressure sensors and temperature
sensors)
Sets address for cool/heat unified operation.
Address for low noise/demand operation
Used to conduct test operation without making changes
to the PCB and replacing the refrigerant, after the
completion of maintenance.
Allows forced operation of indoor unit fan while unit is
stopped. (H tap)
Allows forced operation of indoor unit. (Forced thermostat
ON)
Target evaporation temperature for cooling
Target condensation temperature for heating
Changes the temperature condition for defrost and sets to
quick defrost or slow defrost.
Sets sequential operation
(Factory setting to ON)
Reception of external low noise or demand signal
Set the address for AIRNET.
water heater.
Make this setting in the case of operating in high static
pressure mode with diffuser duct mounted.
(In order to mount the diffuser duct, remove the cover
from the outdoor unit fan.)
If the compress has a failure, used to prohibit the
operation of STD compressor and to conduct emergency
operation of the system with other compressor.
Carries out additional refrigerant charging operation.
Sets to refrigerant recovery or vacuuming mode.
Sets automatic low night noise operation in a simple way.
The operating time is based on "Starting set" and "Ending
set".
Sets low noise level when the low noise signal is input
from outside.
Sets starting time of low night noise operation.
(Low night noise setting is also required.)
Sets ending time of low night noise operation.
(Low night noise setting is also required.)
Used for trouble diagnosis of DC compressor. Since the
waveform of inverter is output without wiring to the
compressor, it is convenient to probe whether the trouble
comes from the compressor or PCB.
If the capacity control is required, the low noise control is
automatically released by this setting during carrying out
low noise operation and low night noise operation.
Changes target value of power consumption when
demand control 1 is input.
Normally enables demand control 1 without external
input. (Effective to prevent a problem that circuit breaker
of small capacity is shut down due to large load.)
73