Daikin VRV II-Q RQYQ8-48PY1B Service Manual page 66

R-410a 50hz heat pump
Table of Contents

Advertisement

Detailed Control Functions
2.5.5 STD Compressor Overload Protection
This control is used to prevent abnormal heating due to overcurrent to the compressor resulting from failures
of STD compressor such as locking.
56
STD compressor ON
Demand to operate.
STD compressor OFF for 30 min.
(2 times per 90 minutes at max.)
CT detection current value>28.8A
Stop due to error
E6
("
" displayed)
SiBE341027
Function

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents