SiBE341027
2.23 Overcurrent Abnormal of Inverter Compressor
L8
Remote
Controller
Display
Applicable
RQYQ-PY1B
Models
Method of Error
Error is detected from the current flowing in the power transistor.
Detection
Error Decision
When the inverter secondary current value is below.
(1) 33.5A and over continues for 5 seconds.
Conditions
(2) 27.6A and over continues for 260 seconds.
Supposed
Causes
Service Diagnosis
Compressor overload
Compressor coil disconnected
Defective wiring to the compressor
Defective inverter PCB
Troubleshooting by Remote Controller
139