2.2 Compressor PI Control

Compressor PI Control

Carries out the compressor capacity PI control to maintain Tc at constant during heating
operation to ensure stable unit performance.
Outdoor compressor (R-410A)
STn
INV(Fullload) INV(Unload)
1
2
3
4
5
6
52.0Hz
7
57.0Hz
8
62.0Hz
9
68.0Hz
10
74.0Hz
 Compressors may operate in a pattern other than those listed in above tables subject to the operating conditions.
Selection of full load operation to/from unload operation is made with the unload circuit solenoid valve
(Y3S=SVUL). The full load operation is performed with the SVUL set to OFF, while the unload operation is
performed with the SVUL set to ON.
Indoor compressor (R-134a)
STEP
INV
1
40.0Hz
2
46.0Hz
3
52.0Hz
4
57.0Hz
5
62.0Hz
6
68.0Hz
7
74.0Hz
8
80.0Hz
9
86.0Hz
10
92.0Hz
11kW -> max. 21 steps
14kW -> max. 26 steps
16kW -> max. 30 steps
48
STn
INV(Fullload) INV(Unload)
36.0Hz
11
39.0Hz
12
43.0Hz
13
47.0Hz
14
52.0Hz
15
57.0Hz
16
64.0Hz
17
71.0Hz
18
78.0Hz
19
20
STEP
INV
11
98.0Hz
12
104.0Hz
13
110.0Hz
14
116.0Hz
15
122.0Hz
16
128.0Hz
17
134.0Hz
18
138.0Hz
19
144.0Hz
20
152.0Hz
80.0Hz
86.0Hz
92.0Hz
98.0Hz
104.0Hz
110.0Hz
116.0Hz
122.0Hz
128.0Hz
134.0Hz
STEP
INV
21
158.0Hz
22
164.0Hz
23
170.0Hz
24
174.0Hz
25
182.0Hz
26
188.0Hz
27
194.0Hz
28
200.0Hz
29
206.0Hz
30
210.0Hz
ESIE09-08B
STn
INV(Fullload) INV(Unload)
21
140.0Hz
22
146.0Hz
23
152.0Hz
24
158.0Hz
25
164.0Hz
26
170.0Hz
27
175.0Hz
28
180.0Hz
29
185.0Hz
30
190.0Hz
Function