Power Supply Insufficient Or Instantaneous Failure - Daikin VRV II-Q RQYQ8-48PY1B Service Manual

R-410a 50hz heat pump
Table of Contents

Advertisement

Troubleshooting by Remote Controller

2.31 Power Supply Insufficient or Instantaneous Failure

U2
Remote
Controller
Display
Applicable
RQYQ-PY1B
Models
Method of Error
Detection of voltage of main circuit capacitor built in the inverter PCB and power supply voltage.
Detection
Error Decision
When the voltage aforementioned is not less than 190V.
Conditions
Supposed
Causes
152
Power supply insufficient
Instantaneous power failure
Open phase
Defective inverter PCB
Defective outdoor service monitor PCB
Defective compressor
Defective main circuit wiring
Defective fan motor
Defective connection of signal cable
SiBE341027
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading