Momentary Overcurrent Of Inverter Compressor - Daikin VRV II-Q RQYQ8-48PY1B Service Manual

R-410a 50hz heat pump
Table of Contents

Advertisement

SiBE341027

2.22 Momentary Overcurrent of Inverter Compressor

L5
Remote
Controller
Display
Applicable
RQYQ-PY1B
Models
Method of Error
Error is detected from the current flowing in the power transistor.
Detection
Error Decision
When an excessive current (59.1A) flows in the power transistor.
(Instantaneous overcurrent also causes activation.)
Conditions
Supposed
Causes
Service Diagnosis
Defective compressor coil (disconnected, defective insulation)
Compressor startup error (mechanical lock)
Defective inverter PCB
Troubleshooting by Remote Controller
137

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents