Compressor Instantaneous Overcurrent - Daikin VRV RXYMQ-A Series Service Manual

R-410a heat pump 50/60 hz
Table of Contents

Advertisement

Troubleshooting by Error Code

5.42 Compressor Instantaneous Overcurrent

Applicable
All outdoor unit models
Models
L5
Error Code
Method of Error
Detect current flowing through the power transistor.
Detection
Error Decision
The current instantaneously exceeds A (A) in the power transistor.
Conditions
Trigger point
2Y350APAX2N
2Y420AVAY1N
Supposed
 Defective compressor coil (such as wiring disconnection or insulation failure)
Causes
 Compressor startup failure (mechanical lock)
 Defective outdoor unit main PCB (RXYMQ4AVMK)
 Defective inverter PCB (RXYMQ4-6AYFK)
Troubleshooting
Power OFF
224
Compressor model
A (A)
48.1
48.55
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Is the stop valve open?
YES
Check for the leads of the
compressor.
• For compressor M1C
Are the
leads of the
compressor normal?
YES
Are
wiring and wire
connections to the
compressor
normal?
YES
A
NO
NO
NO
SiME332106E
Open the stop valve.
Replace the leads of the
compressor.
Rectify the wiring and
wire connections.
Part 6 Service Diagnosis