4.29 "L5" Momentary Overcurrent of Inverter Compressor

L5
Remote
Controller
Display
Applicable
RZQ
Models
Method of
Malfunction is detected by converting the current flowing in the power transistor.
Malfunction
Detection
Malfunction
When an excessive current flows in the power transistor (32.3A).
Decision
Conditions
Supposed
Causes
Troubleshooting
Faulty compressor coil (disconnection, poor insulation)
Compressor startup malfunction (mechanical lock)
Faulty outdoor inverter PC board
Instantaneous power failure
Lightning surge