Troubleshooting by Indication on the Remote Controller
3.30 Momentary Overcurrent of Inverter Compressor
L5
Error Code
Applicable
RWEYQ72P, 84P
Models
Method of Error
Error is detected from current flowing in the power transistor.
Detection
Error Decision
When an excessive current flows in the power transistor
(Instantaneous overcurrent also causes activation.)
Conditions
Defective compressor coil (disconnected, defective insulation)
Supposed
Compressor startup error (mechanical lock)
Causes
Defective inverter PCB
202