Appendix 5 Compliance With The Radio Waves Act (South Korea) - Mitsubishi Electric FR-A720-0.4K Instruction Manual

Fr-a700 series
Hide thumbs Also See for FR-A720-0.4K:
Table of Contents

Advertisement

(2) Low Voltage Directive
We have self-confirmed our inverters as products compliant to the Low Voltage Directive (Conforming standard EN 50178) and affix the CE
marking on the inverters.
Outline of instructions
* Do not use an earth leakage current breaker as an electric shock protector without connecting the equipment to the earth. Connect the
equipment to the earth securely.
* Wire the earth terminal independently. (Do not connect two or more cables to one terminal.)
* Use the cable sizes on page 14 under the following conditions.
⋅ Surrounding air temperature: 40°C maximum
If conditions are different from above, select appropriate wire according to EN60204 Appendix C TABLE 5.
* Use a tinned (plating should not include zinc) crimping terminal to connect the earth (ground) cable. When tightening the screw, be
careful not to damage the threads.
For use as a product compliant with the Low Voltage Directive, use PVC cable whose size is indicated on page 14.
* Use the moulded case circuit breaker and magnetic contactor which conform to the EN or IEC Standard.
* When using an earth leakage current breaker, use a residual current operated protective device (RCD) of type B (breaker which can
detect both AC and DC). If not, provide double or reinforced insulation between the inverter and other equipment, or put a transformer
between the main power supply and inverter.
* Use the inverter under the conditions of overvoltage category II (usable regardless of the earth (ground) condition of the power supply),
overvoltage category III (usable with the earthed-neutral system power supply, 400V class only) and pollution degree 2 or lower
specified in IEC664.
⋅ To use the inverter of 30K or higher (IP00) under the conditions of pollution degree 2, install it in the enclosure of IP 2X or higher.
⋅ To use the inverter under the conditions of pollution degree 3, install it in the enclosure of IP54 or higher.
⋅ To use the inverter of 22K or lower (IP20) outside of an enclosure in the environment of pollution degree 2, fix a fan cover with fan
cover fixing screws enclosed.
FR-A720-1.5K to 3.7K
FR-A740-2.2K, 3.7K
* On the input and output of the inverter, use cables of the type and size set forth in EN60204 Appendix C.
* The operating capacity of the relay outputs (terminal symbols A1, B1, C1, A2, B2, C2) should be 30VDC, 0.3A. (Relay outputs have
basic isolation from the inverter internal circuit.)
* Control circuit terminals on page 9 are safely isolated from the main circuit.
* Environment
Surrounding air
temperature
Ambient humidity
Maximum altitude
Details are given in the technical information "Low Voltage Directive Conformance Guide" (BCN-A21041-203). Please contact your sales
representative.

Appendix 5 Compliance with the Radio Waves Act (South Korea)

This product complies with the Radio Waves Act (South Korea).
Note the following when using the product in South Korea.
(The product is for business use (Class A) and meets the electromagnetic compatibility requirements. The seller and
the user must note the above point, and use the product in a place except for home.)
Fan cover
fixing screw
Fan cover
Fan
FR-A720-5.5K to 11K
FR-A740-5.5K to 15K
During Operation
-10°C to +50°C
90% RH or less
1000m
Fan cover
fixing screws
Fan cover
Fan
FR-A720-15K to 22K
FR-A740-18.5K, 22K
In Storage
-20°C to +65°C
90% RH or less
1000m
Fan cover
fixing screw
Fan cover
Fan
During Transportation
-20°C to +65°C
90% RH or less
10000m
197

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents