Parameter
Name
286
Droop gain
Droop filter time
287
constant
Droop function
288
activation selection
Pulse train I/O
291
selection
Input pulse division
384
scaling factor
Frequency for zero
385
input pulse
Frequency for
386
maximum input pulse
292, 293
Refer to Pr. 61.
294
Refer to Pr. 261.
296
Password lock level
Password lock/
297
unlock
299
Refer to Pr. 57.
Incre-
Initial
Range
ments
Value
0
Droop control is invalid
Set the drooping amount at the rated
0.1%
0%
0.1 to
torque as a percentage with respect to the
100%
rated frequency.
Set the time constant of the primary delay
0.01s
0.3s
0 to 1s
filter applied to the torque current.
Real sensor less
vector/vector control
Droop control is not
exercised during
acceleration/
deceleration.
0, 10
(When Pr.288 = 10,
droop compensation
amount is determined
using the motor
speed as reference.)
Droop control is
1
0
always exercised
during operation.
(with 0 limit)
1, 11
(When Pr.288 = 11,
droop compensation
amount is determined
using the motor
speed as reference.)
Droop control is
always exercised
2
during operation.
(without 0 limit)
0
JOG terminal
1
Pulse train input
10
JOG terminal
11
Pulse train input
20
JOG terminal
1
0
21
Pulse train input
100
Indicates division scaling factor to the input
1
0
0 to 250
pulse and the frequency resolution to the
input pulse changes according to the value.
Set the frequency when the input pulse is 0
0.01Hz
0
0 to 400Hz
(bias).
Set the frequency when the input pulse is
0.01Hz
60Hz
0 to 400Hz
maximum (gain).
0 to 6, 99,
Select restriction level of parameter
100 to 106,
reading/ writing when a password is
1
9999
registered.
199
9999
No password lock
1000 to 9998 Register a 4-digit password
Displays password
unlock error count.
1
9999
(0 to 5)*
(Reading only)
(Valid when Pr. 296 =
"100" to "106, 199")
9999*
No password lock
Parameter List
Description
Advanced magnetic
flux vector control
Droop control is not
exercised during
acceleration/
deceleration.
Droop
compensation
amount is
determined using
the rated motor
frequency as
reference.
Input
Output
FM output
FM output
Pulse train open
collector output
(50% duty)
Pulse train open
collector output
(ON width is always
same)
Pulse train open
collector output
(ON width is always
same
(independently of
Pr. 54))
* "0 or 9999" can be
set in Pr. 297 at any
time although the
setting is invalid
(the displayed value
does not change).
: enabled
× : disabled
×
3
×
×