Parameter
Name
DU/PU main display
52
data selection
FM terminal
54
function selection
AM terminal
158
function selection
Watt-hour meter
170
clear
Operation hour
171
meter clear
Monitor decimal
268
digits selection
Energization time
563
carrying-over times
Operating time
564
carrying-over times
AM output filter
867
Cumulative power
monitor digit shifted
891
times
Incre-
Initial
Range
ments
Value
0, 5 to 14,
Select monitor to be displayed on the operation
panel and parameter unit and monitor to be
17 to 20,
output to the terminal FM and AM.
22 to 25,
1
0
0 : Output frequency (Pr. 52)
32 to 35, 39,
1 : Output frequency (Pr. 54, Pr. 158)
46, 50 to 57,
2 : Output current (Pr. 54, Pr. 158)
100
3 : Output voltage (Pr. 54, Pr. 158)
5 : Frequency setting value
1 to 3, 5 to
6 : Running speed
14, 17, 18,
7 : Motor torque
1
1
21, 24,
8 : Converter output voltage
32 to 34, 46,
9 : Regenerative brake duty
50, 52, 53
10 : Electronic thermal relay function load
11 : Output current peak value
12 : Converter output voltage peak value
13 : Input power
14 : Output power
17 : Load meter
18 : Motor excitation current
19 : Position pulse
20 : Cumulative energization time (Pr. 52)
21 : Reference voltage output (Pr. 54, Pr. 158)
22 : Orientation status
23 : Actual operation time (Pr. 52)
24 : Motor load factor
25 : Cumulative power (Pr. 52)
32 : Torque command
33 : Torque current command
1 to 3,
34 : Motor output
5 to 14, 17,
35 : Feedback pulse
1
1
18, 21, 24,
39 : SSCNET III communication status
32 to 34, 46,
46 : Motor temperature
50, 52, 53
50 : Power saving effect
51 : Cumulative saving power (Pr. 52)
52 : PID set point
53 : PID measured value
54 : PID deviation (Pr. 52)
55 : Input/output terminal status (Pr. 52)
56 : Option input terminal status (Pr. 52)
57 : Option output terminal status (Pr. 52)
100 : Set frequency is displayed during a
*1 Available only when FR-A7AP/FR-A7AL
*2 Available only when FR-A7NS is mounted.
*3 Available only when FR-A7AZ is mounted
0
Set "0" to clear the watt-hour meter monitor.
Sets the maximum value for the monitoring
10
1
9999
from communication to 9999kWh.
Sets the maximum value for the monitoring
9999
from communication to 65535kWh.
Set "0" to clear the operation time monitor.
1
9999
0, 9999
Setting "9999" has no effect.
0
Displays the monitor as integral value.
1
9999
1
Displays the monitor in increments of 0.1.
9999
No fixed decimal position
The numbers of cumulative energization time
(0 to
1
0
monitor exceeded 65535h is displayed.
65535)
Reading only
The numbers of operation time monitor
(0 to
1
0
exceeded 65535h is displayed.
65535)
Reading only
0.01s
0.01s
0 to 5s
Set the output filter of terminal AM.
Set the number of times to shift the
0 to 4
cumulative power monitor digit.
Clamps the monitor value at maximum.
1
9999
No shift
9999
Clears the monitor value when it exceeds
the maximum value.
Description
factor
(Pr. 52)
*1
(Pr. 52)
*1
(Pr. 52)
*1
*3
stop and output frequency is
displayed during operation (Pr. 52)
is mounted.
and SFV5RU
T/A is used.
Parameter List
: enabled
× : disabled
*2
×
×
×
×
×
×
×
×
×
×
103
3