Fresh Air Kit (Optional); Outside Air Installation - Enerzone Solution 2.5ZC Installation Instructions Manual

Hide thumbs Also See for Solution 2.5ZC:
Table of Contents

Advertisement

2.6

FRESH AIR KIT (OPTIONAL)

During operation, the fireplace requires fresh air for combustion and draws air out of the
house. It may starve other fuel burning appliances such as gas or oil furnaces. As well,
exhaust fans may compete for air, causing negative pressure in the house, resulting in smoke
entering the house from the fireplace. This situation is aggravated in modern airtight houses.
To overcome this problem, we strongly recommend that you install fresh air kit (not
included). Check with local authorities having jurisdiction in your area, it may be
mandatory.

2.6.1 Outside Air Installation

The fresh air kit may be installed according to the following requirements:
A) Insulated duct length should be sufficient to avoid condensation.
B) The outside wall termination must not be installed more than 10 ft. (3 m) above the
base of the fireplace.
C) The fresh air must come from outside the house. The air intake must not draw air from
the attic, from the basement, or from a garage.
D) The outside wall termination should be installed where it is not likely to be blocked by
snow or exposed to extreme wind and away from automobile exhaust fumes, gas
meter and other vents.
E) The outside termination may be installed above or below floor level.
F) If more fresh air is needed (airtight house or conduit exceeding 10 ft or 3 m), two
intakes may be installed, providing twice the quantity of incoming fresh air; you may
also increase both conduits to 4 inches, with the use of a 3 to 4 inch adaptor, again
increasing substantially the quantity of incoming fresh air.
The fresh air kit contains the following components:
1- A 3" flex adapter;
2- 2 pipe clamps;
3- An outside air register;
To complete the fresh air kit installation, you will need a 3" insulated flexible pipe. Use the
length required for your installation while respecting the maximum length of 10 ft. (3 m).
Make a 3 1/4" (83 mm) hole in the outside wall of the house at the chosen location. From
outside, place the outside air register in the hole (open side down) and fasten the register to
the wall, with screws as shown (see figure 27). Place the insulated pipe over the register tube
and over the fireplace's outside air connector (see figure 28). At each end, carefully pull back
the insulation and plastic cover, exposing the flexible pipe. Attach the flexible pipe using pipe
clamps. For a better seal, you may also use aluminum tape. Wrap the tape around the joint
between the flexible pipe and the air inlets. Carefully push the insulation and plastic cover
back over the pipe. Fix the plastic in place using aluminum tape.
4- Plate for room air intake;
5- 6 screws;
6- 3" to 4" adaptor.
31

Advertisement

Table of Contents
loading

Table of Contents