Troubleshooting by Remote Controller
4.35 Field Setting Switch Abnormality
UA
Remote
Controller
Display
Applicable
All models of indoor unit
Models
Method of Error
Detection
Error Decision
Incorrect combination indoor unit and outdoor unit
Conditions
Improper field setting
Supposed
Defective indoor unit PCB and wrong wiring
Causes
Defective power supply PCB connection
Indoor-outdoor, indoor-indoor unit transmission wiring
Defective remote controller wiring
Defective indoor unit PCB
Failure for setting the number of simultaneous multi-units
Wrong wiring of crossing transition wire
Defective multi remote controller connection
Faulty connection of optional equipment
186
ESIE12-06
Service Diagnosis