Daikin ZQG71~140L7V1B Service Manual page 94

Skyair gqi-eco series heat pump r-410a 50hz
Table of Contents

Advertisement

Field Setting from Remote Controller
Automatic Operation Mode Control
When selecting "Automatic Operation Mode" with the remote controller, conducts the most
comfortable operation in which you do not feel too cool or too hot.
Automatic Restart after Power Failure Reset
For the air conditioners with no setting for the function, the units will be left in the stop condition
when the power supply is reset automatically after power failure reset or the main power supply
is turned on again after once turned off. However, for the air conditioners with the setting (same
as factory setting), the units may start automatically after power failure reset or the main power
supply turned on again (return to the same operation condition as that of before power failure).
For the above reasons, when the unit is set enabling to utilize "Auto restart function after power
failure reset", utmost care should be paid for the occurrence of the following situation.
Caution 1. The air conditioner starts operation suddenly after power failure reset or
2. In the service work, for example, turning off the main power switch during
Setting of Normal Airflow
Make the following setting according to the ceiling height. The setting position No. is set to "01"
at the factory.
 FCQG71
 FCQG100-140
 FHQG71
 FHQG100-140
82
Outdoor air temperature
Indoor air temperature
Temperature set by remote controller
the main power supply turned on again. Consequently, the user might be
surprised (with question for the reason why).
the unit is in operation, and turning on the switch again after the work is
completed start the unit operation (the fan rotates).
Mode No.
First code No.
13 (23)
Mode No.
First code No.
13 (23)
Mode No.
First code No.
13(23)
Mode No.
First code No.
13(23)
Calculates and controls the optimum indoor
temperature
Second code No.
01
0
02
03
Second code No.
01
0
02
03
Second code No.
01
0
02
Second code No.
01
0
02
ESIE12-06
Ceiling height (m)
 2.7
2.7 - 3.0
3.0 - 3.5
Ceiling height (m)
 3.2
3.2 - 3.6
3.6 - 4.2
Ceiling height (m)
 2.7
2.7 - 3.5
Ceiling height (m)
 3.8
3.8 - 4.3
Field Setting

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rzqsg71-140l7v1bRzqsg71-140l7y1bRzqg71-140l7y1b

Table of Contents