Troubleshooting by Remote Controller
4.17 Electronic Expansion Valve Abnormality
E9
Remote
Controller
Display
Applicable
RZQG
Models
Method of Error
The error is detected whether the continuity of electronic expansion valve exist or not.
Detection
The error is detected by the suction pipe superheat degree, discharge pipe superheat
Error Decision
No common power supply when the power is ON.
Conditions
When the following conditions are met
Supposed
Defective electronic expansion valve
Causes
Disconnection of electronic expansion valve harness
Defective connection of electronic expansion valve connector
Defective each thermistor and mounting thermistor
Defective pressure sensor
Defective outdoor unit PCB
Abnormal wet operation
156
degree and electronic expansion valve opening degree.
Suction pipe superheat degree < 4°C
Minimum electronic expansion valve opening degree
Discharge pipe superheat degree < 5°C
ESIE12-06
Service Diagnosis