Daikin ZQG71~140L7V1B Service Manual page 67

Skyair gqi-eco series heat pump r-410a 50hz
Table of Contents

Advertisement

ESIE12-06
3.2.7 Compressor Step
The compressor operation frequency is controlled in order to keep a constant evaporation
temperature in cooling and a constant condensing temperature in heating.
t cool = Remote controller set temperature - Indoor return air temperature.
Cooling
Depending on t cool and the cooling load, the target evaporating temperature will be a value
between 2°C and 20°C.
t heat = Indoor return air temperature - Remote controller set temperature.
Heating
Depending on t heat and the heating load, the target condensing temperature will be a value
between 42°C and 54°C. (for RZQG100-140L : 42°C and 50°C)
RZQG71L7V1B RZQG71L7Y1B
2YC63SXD
Motor
6 poles
pole
1
57
2
61.5
3
66
4
72
5
78
6
85.5
7
93
8
102
9
109.5
10
118.5
11
127.5
12
136.5
13
145.5
14
151.5
15
154.5
16
174
17
183
18
192
19
201
20
211.5
21
222
22
232.5
23
243
24
253.5
25
265.5
26
277.5
27
289.5
Function and Control
Compressor frequency
RZQSG100-
125L7V1B
2YC63PXD
2YC63SXD
4 poles
6 poles
38
57
41
63
44
69
48
78
52
87
57
97.5
62
109.5
68
124.5
73
139.5
79
156
85
168
91
183
97
192
101
204
103
216
116
228
122
237
128
246
134
255
141
265.5
148
282
155
297
162
309
169
327
177
185
193
: Maximum frequency in cooling
RZQSG100-
RZQ100-
125L7Y1B
140L7V1B/Y1B
2YC63PXD
2YC90AXD/CXD
4 poles
6 poles
38
54
42
58.5
46
64.5
52
70.5
58
78
65
85.5
73
94.5
83
103.5
93
111
104
118.5
112
127.5
122
138
128
148.5
136
162
144
174
152
189
158
204
164
220.5
170
234
177
249
188
261
198
274.5
206
289.5
218
327
Function Details
RZQSG71L2V1B
2YC63DXD
6 poles
57
61.5
66
72
78
85.5
93
100.5
109.5
118.5
127.5
136.5
145.5
154.5
163.5
174
183
192
201
211.5
222
232.5
55