ESIE12-06
4.21 Outdoor Unit PCB Abnormality
L1
Remote
Controller
Display
Applicable
RZQG
Models
Method of Error
Detect error by current value during waveform output before compressor startup.
Detection
Detect error by current sensor value during synchronized operation at the time of startup.
Detect error using an MP-PAM series capacitor overvoltage sensor.
Error Decision
When over-current is detected at the time of waveform output during operating the
Conditions
When the current sensor error during synchronized operation
When overvoltage occurs in MP-PAM
In case of IGBT error
In case of faulty in E
Supposed
External factor (Noise, etc.)
Causes
Defective outdoor unit fan motor
Broken fuse
Disconnection of compressor
Defective outdoor unit PCB (A1P)
Service Diagnosis
compressor
2
PROM
IPM failure
Current sensor failure
MP-PAM failure
Defective IGBT or drive circuit
2
Defective inverter E
PROM
Troubleshooting by Remote Controller
163