Troubleshooting by Remote Controller
4.16 Outdoor Unit Fan Motor Abnormality
E7
Remote
Controller
Display
Applicable
RZQG
Models
Method of Error
Abnormality of fan motor system is detected according to the fan speed detected by hall IC
Detection
when the fan motor runs.
Error Decision
When the fan runs with speed less than a specified one for 15 seconds or more when the fan
Conditions
When connector detecting fan speed is disconnected
When the error is generated 4 times, the system shuts down.
Supposed
Defective fan motor
Causes
The harness connector between fan motor and PCB is left in disconnected, or faulty
Fan does not run due to foreign matters tangled
Defective the outdoor PCB
Blowout of fuse
External factor (Noise, etc.)
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Is the supply
voltage within the range 180
to 220 VAC ?
YES
Turn OFF the power supply (and wait
for 10 minutes).
Remove the connector for fan motor
once, and then connect it again.
A
154
motor running conditions are met
connector
NO
ESIE12-06
Ask repair so that the supply
voltage will be within the normal
range.
Service Diagnosis