ESIE12-06
4.5
Drain Water Level System Abnormality
A3
Remote
Controller
Display
Applicable
All models of indoor unit
Models
Method of Error
By float switch OFF detection
Detection
Error Decision
The error is generated when the water level reaches its upper limit and when the float switch
Conditions
turns OFF.
Supposed
Defective drain pump
Causes
Improper drain piping work
Drain piping clogging
Defective float switch
Defective indoor unit PCB
Defective short circuit connector X15A on PCB
Service Diagnosis
Troubleshooting by Remote Controller
137