ESIE12-06
4.14 Actuation of Pressure Sensor
E4
Remote
Controller
Display
Applicable
RZQG
Models
Method of Error
[In cooling]
Detection
Detect error by the indoor unit intermediate thermistor (R3T).
[In heating]
Detect error by the intermediate heat exchanger thermistor (R5T).
Error Decision
[In cooling]
Conditions
When the detection pressure is the following value
When the saturated pressure equivalent temperature is –34°C
Supposed
The stop valve is not opened
Causes
Disconnection of outdoor unit intermediate thermistor
Disconnection of indoor unit intermediate thermistor
Defective thermistor
Defective outdoor unit PCB (A1P)
Abnormal drop of low pressure
Service Diagnosis
0.12MPa or less continues for 5 minutes
Troubleshooting by Remote Controller
151