Display Options - Honeywell Ademco Vista-12D Installation And Setup Manual

Table of Contents

Advertisement

PROMPT
9 0 A l m / T r b l P r o c
0
9 0 T R B L S O U N D
0
9 0 A L A R M S O U N D
0
9 0 D i a l D e l a y
0 = N o , 1 = Y e s
9 0 D i s p O p t i o n
1
A l a r m I D :
0 0 0
T r o u b l e I D : 0 0 0
VALID ENTRIES
Alarm/Trouble
Processing
0=none
1=Zone type has automatic
restore
2=zone type uses Misc. Fault
Delay Time and automatic
restore
[∗] to continue
Trouble Sounding
0= none
1= one beep every minute
2= normal trouble sound (fast
beeps)
[∗] to continue
Alarm Sounding
0=none
1= keypad sound only
2= steady siren sounding
3= pulsing siren (temporal)
[∗] to continue
Dial Delay?
0=no
1=yes
[∗] to continue

Display Options

0 = no display
1 = display only
2 = chime only
3 = chime & disp.
[∗] to continue
Contact ID Report Codes
000-999 = report code
[∗] to continue; returns to Enter
configurable zone type number
prompt.
Menu Mode Programming
EXPLANATION
Select desired actions for zones assigned to this
zone type.
Option 2: Select Miscellaneous Fault Delay in
field *87.
NOTE: If 6 was selected above for the Zone
Attribute, enter 0 for this prompt.
Select type of sounding upon trouble conditions on
zones assigned to this zone type.
Select type of sounding upon alarm conditions on
zones assigned to this zone type.
If selected, faults on zones assigned to this zone
type will delay reporting for whatever length of
time that is selected in dial delay (*50).
Select whether faults on zones assigned to this
zone type are displayed at the keypad and/or
cause a chime sound.
Enter the desired 3-digit Contact ID report codes
for faults and troubles occurring on zones assigned
to this zone type.
IMPORTANT: Make sure the code does not
conflict with existing, predefined Contact ID
report codes. See the System Communication
section for a list of standard Contact ID codes.
5-25