Ademco Contact Id - Honeywell Ademco Vista-12D Installation And Setup Manual

Table of Contents

Advertisement

Installation and Setup Guide
Signal flow
Receiving equipment
Send start char 'w' (77h)
Acknowledge ACK (06h)
(Delay greater than 500ms)
Send new start char 'w' (77h)
Acknowledge ACK (06h)
...etc
• Dialer should start sending the message no more than 200ms after start char.
• If no response is detected the receiver retries sending start char three times (in total
four) before hanging up.
• If the receiver reads a message with checksum error it will reply with NAK (15h),
wait more than 500ms and then send a new start char (w).
• The receiver can optionally send a command back to the dialer after ACK.
The command may be one byte with any content except 'w' (77h), ACK (06h) or NAK
(15h)..

ADEMCO Contact ID

ADEMCO and Robofon Contact ID
CCCC(CCCCCC) Q EEE GG ZZZ
where:
CCCC(CCCCCC) = 4-digit or 10-digit Customer (subscriber) ID
Q = 1-digit Event qualifier, where:
EEE = 3-digit (hexadecimal) Event code (see central office receiver manual
GG = 2-digit Partition Number (system messages show "00")
ZZZ = 3-digit Zone/contact ID number reporting the alarm, or user number
6-4
®
®
Reporting takes the following format:
E = new event , and R = restore
for a complete list of event codes)
for open/close reports. System status messages (AC Loss, Walk Test,
etc.) contain zeroes in the ZZZ location.
Dialing equipment
Send message described above
Send next message if available

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents