Zone Type
Type 22: Disarm
(BR RF devices only)
Type 23 *
No Alarm Response
* The system can still be armed when these zone types are in a faulted condition.
Type 24
Silent Burglary
Type 77
Keyswitch
Type 81
AAV Monitor Zone
Type 82
Blockschloss
Types 90-93
Configurable
Description
• Disarms the system when the zone is activated.
• User number for button must be assigned.
• Can be used on a zone when an output relay action is desired, but with
no accompanying alarm (e.g., lobby door access).
• Zone faults/restores are event logged.
• Usually assigned to all sensors or contacts on windows and infrequently
used exterior doors where siren sounding is NOT desired for alarms.
• Provides an instant alarm, with NO audible indication at any keypad or
external sounder, if the zone is faulted when the system is armed in the
Away, Stay, Instant, or Maximum modes.
• A report is sent to the central station.
• Assign to zone wired to a keyswitch.
• Do not use devices assigned as input type "BR" with this zone type.
• Assign to zone connected to AAV module.
• Monitors 2-way voice sessions as follows:
- When the zone is faulted, all alarm sounding and dialer reporting stops,
except
for fire alarms, which immediately terminate the voice session and
cause
a fire report to be sent.
- When the zone is restored (session ended), sounding resumes (if bell
timeout
has not expired) and reports that were stopped are sent.
• Used with special blockschloss lock and key.
• System arms 5 seconds after the key is fully turned (arms MAXIMUM);
key can then be removed.
• When armed, the blockschloss zone is shorted. An open circuit on this
zone causes trouble condition.
• If zones are "not ready," the key will not turn fully and the system will
not arm.
• Contact ID report code is 409.
• Once the system is armed using blockschloss, it can be disarmed only by
the key; wired keypads, RF keypads, and keyfobs cannot be used for
disarming.
• If any zone in the system is assigned as blockschloss zone type, the system
will not arm in AWAY mode. The system can, however, be armed in STAY
or INSTANT modes from keypads and keyfobs even if the blockschloss
zone is faulted.
• Allows for various custom responses.
• Options include response to entry/exit delays, response to opens/shorts,
types of alarm/trouble sounding, dial delay, and unique Contact ID report
codes.
• Use *83 Menu mode to program these configurable zone types.