Honeywell Ademco Vista-12D Installation And Setup Manual page 38

Table of Contents

Advertisement

Installation and Setup Guide
FIELD
TITLE and DATA ENTRIES
RF House ID Code
*24
00 = disable all wireless keypad usage
01–31 = House ID for partition 1, 2, 3
Arming Prevention Override
*25
Entry 1: 0 = no arming prevention override
1 = allow system to arm with an RF
trouble failure
2 = allow system to be armed with
an AC Mains Loss
4 = allow system to be armed with a
system low battery
8 = allow system to be armed with a
phone or comm. failure
Entry 2: 0 = no tamper override***
1
= allow system to be armed with
a tamper fault
2
= allow system to be armed with
a tamper fault once
4 = allow system to be armed with a
bell supervision failure
Chime By Zone / #65 Prog Mode
*26
Entry 1: Chime by Zone
0 = no zone list (chimes on fault of any
entry/exit or perimeter zone when chime
mode on)
1 = use zone list (chimes on fault of
specific zones programmed in zone list
3 when Chime mode on)
Entry 2: #65 Program Mode (for Installer
Code Access)
0 = Installer code can enter programming mode
1 = Installer Code Access disable; System or
Partition Master code can enable Installer
code access by entering [#] + 65
Powerline Carrier Device (X-10)
*27
House ID
0 = A
1 = B
2 = C
3 = D
4 = E
5 = F
Language Select
*28
0 = English
1 = Spanish
4-2
6 = G
# + 11 = L
7 = H
# + 12 = M
8 = I
# + 13 = N
9 = J
# + 14 = O
# + 10 = K
# + 15 = P
2 = Italian
3 = Portuguese
EXPLANATION
The House ID identifies receivers and wireless
keypads. If a 5827 or 5827BD wireless keypad or
5804BD/5804BDV transmitter is being used, a House
ID code must be entered, and the keypad must be set
to the same House ID. You can assign RF house ID for
each partition.
Does not apply to 5839 or 5828/5828V.
If no override is selected, system will not be able to be
armed when there is a supervision failure, system low
battery, AC mains loss, or a tamper condition.
If override is enabled, the user must enter the arming
sequence twice to arm the system; the first entry of
user code + arm command will not arm, but a second
entry of user code +arm command will arm the system.
E.g., To select arm with "supervision failure" and "low
battery", enter 5 (1 + 4)
† NOTE: If tamper option 1 or 2 is selected, field *175
digit 2 must be "0."
*** Must be 0 for prEN50131-3 compliance
Chime by Zone
If enabled, you can define the specific zones intended to
chime when faulted while the system is in Chime
mode. Use zone list 3 to assign these zones (see ∗81
Zone List Programming section for details).
Installer Code Access: Some installations may
require that the Installer cannot access the system
without the end user's permission (EN50131-1
compliance). If selected (Installer code disabled), the
system master or partition master must first enable
the Installer code before it can be used. Once enabled,
the Installer code remains active until any other user
enters their code.
To enable the Installer code: master code + [#] + 65
Powerline Carrier devices require a House ID,
identified in this field. Program Powerline Carrier
devices in interactive modes ∗79, *80 and *81.
Select the desired keypad display language.