5 SETTINGS
ENERVISTA MII SETUP
Phase TOC Function
PHASE TOC 51P
51P Permission to Trip
Trip Enable 51P
51P Pickup Value
Pickup 51P
51P Curve Type
Curve 51P
51P Time Dial
TD mult 51P
51P Definite Time Delay
Def Time 51P
Ground TOC Function
GROUND TOC 51G
51G Permission to Trip
Trip Enable 51G
51G Pickup (for 1/5 A
Pickup 51G
ground)
51G Pickup (for sensitive
Pickup 51G
ground)
51G Curve Type
Curve 51G
51G Time Dial
TD Mult 51G
51G Definite Time Delay
Def Time 51G
PHASE / GROUND IOC SETTINGS (50P1 / 50P2 / 50G1/50G2) (
ENERVISTA MII SETUP
Phase IOC High Setting
50P1 Function
50P1 Permission to Trip
50P1 Trip
50P1 Tap / Pickup
50P1 Pickup
50P1 Time Delay
50P1 Time Delay
Phase IOC Low Setting
50P2 Function
50P2 Permission to Trip
50P2 Trip
50P2 Tap / Pickup
50P2 Pickup
50P2 Time Delay
50P2 Time Delay
Ground IOC High Set.
50G1 Function
50G1 Permission to Trip
50G1 Trip
50G1 Tap / Pickup (for 1/5 A
50G1 Pickup
ground)
GEK-106237P

5.2.2 PHASE / GROUND TOC SETTINGS (51P / 51G) (

HMI
DEFAULT
PHASE TOC 51P
Trip Enable 51P
No
Pickup 51P
0.5 In (Phase)
Curve 51P
DEFINITE TIME DEFINITE TIME,
TD mult 51P
0.5
5
0.5
Def Time 51P
1.00 s.
GROUND TOC 51G
Trip Enable 51G
No
Pickup 51G
0.5 In (Ground)
Pickup 51G
0.005 A
Curve 51G
DEFINITE TIME DEFINITE TIME,
TD Mult 51G
0.5
5
0.5
Def Time 51G
1.00 s.
HMI
DEFAULT
Phase IOC 50P1
Trip Enable 50P1
No
Pickup 50P1
1 In (Phase)
Delay 50P1
0 s.
Phase IOC 50P2
Trip Enable 50P2
No
Pickup 50P2
1 In (Phase)
Delay 50P2
0 s.
Ground IOC 50G1
Trip Enable 50G1
No
Pickup 50G1
1 In (Ground)
MIFII Digital Feeder Relay
5.2 MAIN SETTINGS
RANGE
STEP
Yes/No
NA
0.1-2.4 In (Ph)
0.01 In (Ph)
NA
USER, MOD
INVERSE, VERY
INVERSE, EXTR
INVERSE, INVERSE
SHORT, INVERSE
LONG
0.05 – 2.00
0.01
(IEC curves)
0.5 – 20.0
0.01
(ANSI curves)
0.5 – 10.0
0.01
(IAC curves)
0.00 – 600.00 s.
0.01 s.
Yes/No
NA
0.10 – 2.40 In (Gnd)
0.01 In
(Gnd)
0.005-0.12 A
0.001 A
NA
USER, MOD
INVERSE, VERY
INVERSE, EXTR
INVERSE, INVERSE
SHORT, INVERSE
LONG
0.05 – 2.00
0.01
(IEC curves)
0.5 – 20.0
0.01
(ANSI curves)
0.5 – 10.0
0.01
(IAC curves)
0 –600.00s.
0.01 s.
RANGE
STEP
Yes/No
NA
0.1 – 30.0 In (Ph)
0.1 In (Ph)
0 – 600.00 s.
0.01 s.
Yes/No
NA
0.1 – 30.0 In (Ph)
0.1 In (Ph)
0 – 600.00 s.
0.01 s.
Yes/No
NA
0.1 – 30 In (Gnd)
0.1 In (G)
5