C.3 COMMAND EXECUTION
Example:
We send the Group-related command. For instance, to activate Group 2, the selection command will be 15 (0F00H)
Intel Request:
ADDRESS
01H
Intel Reply:
ADDRESS
01H
C
CONFIRMATION:
Intel Request:
Intel Reply:
Motorola Request:
C-4
FUNCTION
BEGINNING
10H
0000H
FUNCTION
10H
FIELD
Relay address
Function
Beginning address
Number of registers
Number of bytes
Value of the registers
CRC
FIELD
Relay address
Function
Beginning address
Number of registers
CRC
FIELD
Relay address
Function
Beginning address
Number of registers
Number of bytes
Value of the registers
CRC
#REGS
#BYTES
0001H
02H
BEGINNING
#REGS
0000H
0001H
LENGTH
1 byte
1 byte (10H)
1 word (0000H) (High byte – low byte)
1 word (0001H) (High byte – low byte)
1 byte (06H)
Register1=>Command code (Low byte – High
byte).
Register2=>Relay password (Low byte – High
byte).
Register3=>Constant value
1 word
LENGTH
1 byte
1 byte (10H)
1 word (0000H) (High byte – low byte)
1 word (0003H) (High byte – low byte)
1 word
LENGTH
1 byte
1 byte (10H)
1 word (000H) (High byte – low byte)
1 word (0001H) (High byte – low byte)
1 byte (02)
Register1=>Command code (Low byte – High
byte).
1 word
MIFII Digital Feeder Relay
APPENDIX C
DATA0
CRC
0F00H
A3A0H
CRC
01C9H
GEK-106237P