GE MIFII GEK-106237P Instruction Manual page 158

Digital feeder protection with recloser
Table of Contents

Advertisement

9 RELAY COMMISSIONING
ENERVISTA MII SETUP HMI
50G1 Tap / Pickup (for
50G1 Pickup
sensitive ground)
50G1 Time Delay
50G1 Time Delay
Ground IOC Low Setting
50G2 Function
50G2 Permission to Trip
50G2 Trip
50G2 Tap / Pickup (for 1/5
50G2 Pickup
A ground)
50G2 Tap / Pickup (for
50G2 Pickup
sensitive ground)
50G2 Time Delay
50G2 Time Delay
Thermal Image (49)
49 Function
Permission to Trip
49 Trip
49 Tap / Pickup
49 Pickup
Overload Percent Alarm
49 Alarm Level
Heating Time Constant τ1 T1
Cooling Time Constant τ2 T2
Autorecloser (79)
AUTORECLOSER 79
Autorecloser Function
Autorecloser Function
Number of shots
Number of shots
reclosure AR Dead Time Shot 1
st
Delay before 1
AR Dead Time Shot 2
nd
Delay before 2
reclosure
reclosure AR Dead Time Shot 3
rd
Delay before 3
reclosure AR Dead Time Shot 4
th
Delay before 4
Time delay to reset from
AR Reset Lockout Time
lockout status
Time for incomplete
AR Incomplete
sequence
Sequence Time
Recloser reset time after a
AR Reset Time
successful reclosure
Permission for 50P1 to
AR 50P1 Permission Init AR 50P1 Init
Init Autorecloser
Permission for 50G1 to
AR 50G1 Permission Init AR 50G1 Init
Init Autorecloser
Permission for 50P2 to
AR 50P2 Permission Init AR 50P2 Init
Init Autorecloser
Permission for 50G2 to
AR 50G2 Permission Init AR 50G2 Init
Init Autorecloser
Permission for 51P to Init
AR 51P Permission Init
Autorecloser
Permission for 51G to Init
AR 51G Permission Init
Autorecloser
Permission for 49 to Init
AR 49 Permission Init
Autorecloser
Permission for a DI to Init
AR External Permission
Autorecloser
Init
GEK-106237P
USER
SETTING
Pickup 50G1
Delay 50G1
Ground IOC 50G2
Trip Enable 50G2
Pickup 50G2
Pickup 50G2
Delay 50G2
THERMAL MODEL 49
Trip Enable 49
Pickup 49
Alarm Level 49
Heat Time 49
Cool Time 49
AUTORECLOSER 79
AR Function
AR Max Shots
AR Dead Time 1
AR Dead Time 2
AR Dead Time 3
AR Dead Time 4
AR Rst LO Delay
AR Inc Seq Time
AR Reset Time
AR 51P Init
AR 51G Init
AR 49 Init
AR EXTERN Init
MIFII Digital Feeder Relay
9.19 USER SETTINGS
RANGE
0.005-0.12 A
0 – 600.00 s.
Yes/No
0.1 – 30 In (Gnd)
0.005-0.12 A
0 – 600.00 s.
Yes/No
0.10 – 2.4 In (Ph)
70% – 100% ITH
3 – 600 min.
1 – 6 times τ1
Yes / No
1 – 4
0.1 – 600
0.1 – 600
0.1 – 600
0.1 – 600
0.1 – 600
0.1 – 600
0.1 – 600
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
STEP
0.001 A
0.01 s.
NA
0.1 In (G)
0.001 A
0.01 s.
NA
0.01 In (Ph)
1%
1 min
1
N/A
1
0.01
0.01
0.01
0.01
0.01
0.01
0.01
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
9
9-27