9.14 GROUND IOC LOW SETTING ELEMENT (50G2)

9 RELAY COMMISSIONING
9.14GROUND IOC LOW SETTING ELEMENT (50G2)
Enable only 50G2 element.
Set time delay as needed. If time delay is set to 0 sec., relay operating time will be between 10 to 50 ms. Also, the customer
has to test pickup.
With 0.9 times the pickup current the relay should not trip.
With 1.1 times the pickup current the relay should trip in between 10 to 50 ms.
With 4 times the pickup current the relay should trip in between 10 to 40 ms.
9
9-14
MIFII Digital Feeder Relay
GEK-106237P