Optional Parts Wiring; External Input And External Output (Optional Parts) - Fujitsu AIRSTAGE ABUA12TLAV2 Installation Manual

Indoor unit (floor / ceiling type)
Table of Contents

Advertisement

(3) Remove the elec-
tric component
box cover.
Remove the 3 tap-
ping screws.
Be careful not to pinch the lead cables between the electric component box and base.
(4) Wiring
* When there is 1 transmission cable or remote controller cable, fasten it the same way as
shown in the figure with a cable tie (medium).
When switching the DIP switch (SW1), be sure to turn off the power supply to the indoor
unit. Otherwise, the PC board of the indoor unit may be damaged.
• Fix the conduit with the supporters as shown below.
Conduit (power supply cable)
Indoor unit
30 in
(756 mm)
or less

6.5. Optional parts wiring

6.5.1. Layout of the indoor unit PCB
Do not operate any switches other than prescribed, as it can cause the unit to operate
improperly or malfunction.
Use an insulated screwdriver to set the DIP switches.
Controller PCB
DIP switch
(SET 2)
ON
OFF
SW4
CN65
SW3
SW2
SW1
CN820
En-9
Base
Electric component box cover
CAUTION
CAUTION
Y1, Y2:
Remote controller cable
X1, X2:
Transmission cable
Cable tie (medium)
(accessories)
Conduit (L1, L2(N):
Power supply cable)
Lock nut
Earth (Ground)
Supporter
54 in
54 in
(1,361 mm)
(1,361 mm)
(1,361 mm)
or less
or less
CAUTION
CNA04
Power indicator lamp (green)
Name
Power indicator lamp (green) Indicates the state of the power supply. Refer to "Power
CNA01
CNA03
CNA02
CNA04
DIP switch SET 2 (SW2)
CNB01
CN65
CN820
*1: For details, refer to each installation manual.
6.5.2. Power indicator lamp status
Power indicator lamp (Green)
Lit
Fast flashing (every 0.1 sec-
ond)
Blinking (repeat 3 seconds ON
and 1 second OFF)
6.5.2 Connection methods
Wire modification for External
input/output wire
(1) Remove insulation from wire at-
tached to wire kit connector.
(2) Remove insulation from field
supplied cable. Use crimp type
insulated butt connector to join field
cable and wire kit wire.
(3) Connect the wire with connecting
wire with solder.
Wiring arrangement
In following figure, all the possible connectors are connected for description.
In actual installation, you cannot connect all the connectors at once.
Cable tie (locally purchased)
(bind with other cables)

6.6. External input and external output (optional parts)

6.6.1. External input
• Indoor unit can be Operation/Stop, Emergency stop or Forced stop by using indoor unit
54 in
PCB CNA01 or CNA02.
• "Operation/Stop" mode, "Emergency stop" mode or "Forced stop" mode can be selected
or less
with function setting of indoor unit.
• Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.
• A twisted pair cable (22 AWG) should be used. Maximum length of cable is 492 ft (150 m).
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
Input select
Use either one of these types of terminal according to the application. (Both types of
terminals cannot be used simultaneously.)
● Apply voltage terminal ([CNA01], [CNA03])
When a power supply must be provided at the input device you want to connect, use the
Apply voltage terminal ([CNA01], [CNA03]).
CNB01
CNA01
CNA03
CNA02
indicator lamp status" following.
Apply voltage terminal
Dry contact terminal
Input signal type switching
Output terminal
For one of the following.
• MODBUS® convertor (*1)
• Wireless LAN adapter (*1)
For External power supply unit (*1)
Lit when the power is turned on.
There is a fault with the communication board or the
main board.
The indoor unit is turned off and power is supplied
from the External power supply unit (optional) to the
indoor unit PCB.
IMPORTANT:
Be sure to insulate the connection between the
wires.
Locally purchased
Solder and insulate the connected parts.
DC power supply
12 to 24 V
Load
resistance
(*a)
Load
resistance
(*a)
Load
resistance
(*a)
Connected unit
Application
For external input
For external output
Status contents
Wire kit connector
(optional parts)
Cable tie
(locally purchased)
EMI core (accessory of the
External power supply unit)
P.C.B
(*1)
CNA01
(*b)
CNA03