E: 12.↓. →Ired Remote Controller Communication Error (Indoor Unit) - Fujitsu AUUH18LUAS Service Manual

Cassette type
Table of Contents

Advertisement

2-3. E: 12.X. Wired remote controller communication error
(Indoor unit)
→ired remote
Indicator
controller
Indoor unit
Detective actuator
→ired remote control
Forecast of cause
Check point 1. Check the connection of terminal
After turning off the power, check & correct the followings.
Check the connection of terminal between wired remote controller and indoor unit, and check if
there is a disconnection of the cable.
Check Point 1-2 : Check →ired remote controller and main PCB
Check voltage at CN300 of main PCB (terminal 1—3, terminal 1—2). (Power supply
to the remote controller)
Upon correcting the removed connector or mis-wiring, reset the power.
If it is DC 12 V, remote controller is failure. (Main PCB is normal) => Replace remote control.
If it is DC 0 V, Main PCB is failure. (Check remote controller once again) => Replace Main
PCB.
Check Point 2 : →ire installation wrong remote controller group setting
→rong wire connection in remote controller group (Please refer to the installation manual)
The number of connecting indoor unit and remote controller in one remote controller group
were less than 16 units.
Check Point 2-1 : Check Indoor unit main PCB
Check if main PCB damage
Change main PCB and check the error after setting remote controller address
2-3. E: 12.↓. →ired remote controller communication error (Indoor unit)
Error code
Main PCB
→hen the indoor unit cannot receive the signal from
→ired remote controller more than 1 minute during
normal operation.
End
End
- (03-9) -
E: 12
Terminal connection abnormal
→ired remote control failure
Main PCB failure
2. Troubleshooting with error code