Outdoor Unit Fan Motor Error - Fujitsu ASYA07LBCM Service Manual

Table of Contents

Advertisement

Trouble shooting 14
OUTDOOR UNIT Error Method:

Outdoor Unit Fan Motor Error

Detective Actuators:
Outdoor Unit Inverter PCB Circuit
Outdoor Fan Motor
Forecast of Cause:
1. Fan rotation failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
OK
Check Point 3 : Check Output Voltage of Inverter PCB
Check outdoor unit circuit diagram and the voltage.
(Measure at Inverter PCB side connector)
RED
1
2
3
BLACK
CN800
4
WHITE
5
YELLOW
6
BROWN
7
Read wire
Red - Black
White - Black
If the voltage is not correct, replace Inverter PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When outdoor fan rotation speed is less than 100rpm in 20 seconds
after fan motor starts, fan motor stops.
After fan motor restarts, if the same operation within 60sec is repeated
3 times in a row, compressor and fan motor stops.
If
permanently.
2. Motor protection by surrounding temperature rise
FAN MOTOR
FM
DC voltage
300
400V
15 1.5V
and
repeats 5 times in a row, compressor and fan motor stops
02-17
3. Inverter PCB failure