MTU Gas engine8 V 4000 L62 Operating Instructions Manual page 118

Gas engine 8 v 4000 l62
Table of Contents

Advertisement

151058 – Delta P High Limit Error
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
151059 – FGP High Limit Error
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
151061 – Watchdog Reset
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
151064 – CAN Flow Demand Failed
Red alarm. Initiated by TecJet.
Cause
TecJet setting is not correct.
151066 – TecJet Shutdown
Red alarm. Initiated by TecJet.
Cause
TecJet combined alarm. At least
one additional TecJet alarm is
pending.
151067 – TecJet Internal Fault
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
151069 – Keyswitch State
Red alarm. Initiated by TecJet.
Cause
Keyswitch cabling missing.
118 | Troubleshooting | MS150032/02E 2012-07
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.
Corrective action
u Switch over setting to PWM input. Check PWM signal.
Corrective action
u Rectify the cause of the source alarm.
Corrective action
u Restart TecJet.
Corrective action
u Check cabling.