C- PIPE CONNECTOR
The Mini-Caddy must be connected to a 6" chimney. If draft exceed –0.06 w.c., you must install a barometric
control. The barometric control must be adjusted so that the maximum draft measured at the furnace outlet is
limited to -0.06 in. w.c. Please note that a draft higher than -0.06 W.C. could result in an uncontrollable fire. On the
other hand, the minimum draft to be respected is -0.04 in. w.c. in the evacuation pipe.
For a proper installation, follow the advices below:
1. All the evacuation pipe joints must be secured with three screws.
Make sure that each screw goes through the inner walls of both connectors (male and female). See
pictures below showing a male-female coupling.
PROPER INSTALLATION
IMPROPER INSTALLATION
CAUSES RESTRICTION
2. A minimum rise of 1/4 inch per horizontal foot must be respected.
9