Step 2. Program Protocol for channels 1-8:
a. Select from: Steady, Code 3, Follower Mode, Amseco/Potter, Gentex
Protocol Selection:
LCD
Function
Legend
1a
Steady
2a
Steady
3a
Steady
1b
Code 3
2b
Code 3
3b
Code 3
1c
Follower Mode
2c
Follower Mode
3c
Follower Mode
1d
Amseco/Potter
2d
Amseco/Potter
3d
Amseco/Potter
1e
Reserved
2e
Reserved
3e
Reserved
1f
Gentex
®
2f
Gentex
®
Gentex
®
3f
Gentex is a registered trademark
of Gentex Corporation.
1g
System Sensor
2g
System Sensor
System Sensor
3g
System Sensor is a registered
trademark of Honeywell.
1h
CooperWheelock
2h
CooperWheelock
CooperWheelock
3h
CooperWheelock is a
registered trademark of
CooperWheelock.
Depress the joystick one (1) time from Function screen or two (2) times from Stand-by screen.
Use [UP/DOWN] to select Protocol, Use [Left/Right] to select outputs.
Use [Right] to copy setting to next output.
Class A outputs are paired.
If output is set for Ax or Bx - Protocol settings are not available.
FireSwitch108
Triggered From
Input 1
Input 2
Redundant - Input 1 and Input 2.
Input 1
Input 2
Redundant - Input 1 and Input 2.
Input 1
Input 2
First Input to go in alarm mode.
Input 1 (both horns and strobes). This mode is designed to work with the Amseco/Potter
Input 2 (both horns and strobes).
Input 1 - strobes only,
Input 2 - horns and strobes.
Input 1 (both horns and strobes).
Input 2 (both horns and strobes).
Input 1 - strobes only,
Input 2 - horns and strobes.
Input 1 (both horns and strobes). This mode is designed to work with the Gentex
Input 2 (both horns and strobes).
Input 1 - strobes only,
Input 2 - horns and strobes.
Input 1 (both horns and strobes). This mode is designed to work with the System
®
Input 2 (both horns and strobes).
®
®
Input 1 - strobes only,
Input 2 - horns and strobes.
Input 1 (both horns and strobes). This mode is designed to work with the
®
Input 2 (both horns and strobes).
®
®
Input 1 - strobes only,
Input 2 - horns and strobes.
, System Sensor
®
Description
A steady output signal will be generated. This mode
will accept steady or pulsing input.
Enables Temporal Code 3 signal generation output.
This mode will accept a steady or a pulsing input.
Output follows signal it receives from the
corresponding input (i.e. FACP Sync module -
maximum synchronization of notification
appliance circuit).
series of horns, strobes, and horn/strobes to provide
a means of synchronizing the Temporal-coded horns,
synchronizing the one-second flash timing of
the strobe, and silencing the horns of the horn/strobe
combination over a two-wire circuit while leaving
strobes active.
Reserved
of horns, strobes, and horn/strobes to provide a means
of synchronizing the Temporal-coded horns,
synchronizing the flash timing of the strobe, and
silencing the horns of the horn/strobe combination
over a two-wire circuit while leaving strobes active.
Sensor
series of horns, strobes, and horn/strobes to
®
provide a means of synchronizing the Temporal-coded
horns, synchronizing the flash timing of the strobe, and
silencing the horns of the horn/strobe combination
over a two-wire circuit while leaving strobes active.
CooperWheelock series of horns, strobes, and
horn/strobes to provide a means of synchronizing the
Temporal-coded horns, synchronizing the one-second
flash timing of the strobe, and silencing the horns of
the horn/strobe combination over a two-wire
circuit while leaving strobes active.
or CooperWheelock
.
®
®
series
®
- 9 -