Menvier Security TS590 Installation & Programming Manual page 28

Intruder alarm control panels
Table of Contents

Advertisement

Engineer's Menu 1
12 Monitor Dur.
This timer affects the duration of the "Timed
Output" (No. 042). This timer has a working
range of 000-199 minutes. (Default: 000 Secs)
13 P.Set Bell Dly
This is a "Part-Set Bell Delay" and operates as
follows:
a) If the "Pset Com.Dly" is set to 000 and an
alarm is activated whilst the system is part-set,
the "Bell Delay" timer is started. At the end of the
bell delay the internal sounders are activated
for the duration of the "Pset Bel.Dly". At the end
of this delay the bell output is activated.
b) If the "Pset Com.Dly" is not set to 000 and
an alarm is activated whilst the system is
part-set, the "Bell Delay" timer is cancelled and
the internal sounders are activated for the
duration of the "Pset Bel.Dly". At the end of this
delay the bell output is activated.
If the "Part Set Bell Delay" timer is set to 199 the
bell output is not activated when an alarm
occurs whilst the system is part set. This timer
has a working range of 000 - 199 seconds.
(Default: 000 Secs)
14 Courtesy Dur.
This timer is used to control the duration of the
output type "Courtesy Light". This timer has a
working range of 000-199 seconds. (Default:
030 Secs)
15 No. Rem. Resets
This counter determines how many coded
"Remote Resets" can occur before the system
locks into engineer reset only. Note: Remote
Reset by the "Rem Reset" input terminal is also
affected by this counter. This counter has a
working range of 000-199. (Default: 010)
16 Modem Rings
This counter is for use with the Digicom, it allows
the installer to specify how many rings are
required before the DC6 picks up the call. If the
counter is set to 000 it will pick the call up as
soon as any incoming ringing is detected. This
counter has a working range of 000-199.
(Default: 000)
17 P.I.D Alarms
When using the Digicom and "Point ID
Extended Reporting". The number of point ID
alarms that are transmitted to the central
station per circuit are controlled by the value of
this counter. e.g., if the counter is set to 003
28
then all circuits will report 3 activation's before
they are locked out from sending any more.
Note: this does not affect the re-arm of the
zone. This counter has a working range of 000 -
199. (Default: 005)
18 AC Off Dly
This timer delays the "audible" mains off
indication when the mains power is removed.
The display and any outputs programmed as
"Mains Off" are not affected. This timer has a
working range of 000-199 minutes. (Default:
000 Secs)
19 Test Call
If the system is fitted with a Digicom, it is
possible for the control panel to make the DC6
send a timed test call to the central station. The
"Test Call" timer sets the period of activation,
i.e., 000=Disabled, 001=daily, 007=weekly
etc. Once programmed the digicom will send
the test call at the hour defined by timer 23.
This timer has a working range of 000-199 days.
(Default: 000 Days)
20 2nd Alrm Time
This timer controls the duration of the "Second
Alarm" output. This timer has a working range of
000-199 seconds. (Default: 060 Secs)
21 Line Flt Dly
This timer delays the "audible" line fault
indication when a telephone line fault occurs.
The display and any outputs programmed as
"Line Fault" are not affected. If the timer is set to
199 the monitoring of line fault is disabled. This
timer has a working range of 000-199 minutes.
(Default: 000 Mins)
22 Service Time
The installation company may use this timer to
periodically generate a "SERVICE REQUIRED"
message so that the user is reminded that a
service call is required. The users may continue
to set and unset the system. When the
engineer attends the site and enters their
passcode the message is cleared. The service
timer is re-started when the engineer re-selects
this timer option. To disable this feature set the
timer to 000. This timer has a working range of
000-199 months. (Default: 000 Months)
23 Test Call At
This timer is used in conjunction with timer 19, it
controls the hour at which a test call is sent to
central station. For example, if the timer is set to
TS590 Installation Manual