Inputting, Modifying, and Checking the Program
Example
Error Messages
Message
****REPL ROM
An attempt was made to write to ROM or to write-protected RAM. Be sure a RAM Unit is mounted
and that its write-protect switch is set to OFF.
****PROG OVER
The instruction at the last address in memory is not NOP(00). Erase all unnecessary instructions
at the end of the program or use a larger Memory Unit.
****ADDR OVER
An address was set that is larger than the highest memory in Program Memory. Input a smaller
address
****SETDATA ERR
Data has been input in the wrong format or beyond defined limits, e.g., a hexadecimal value has
been input for BCD. Reinput the data.
****I/O NO. ERR
A data area address has been designated that exceeds the limit of the data area, e.g., an
address is too large. Confirm the requirements for the instruction and reinput the address.
52
The following ladder diagram can be input using the key inputs shown below.
Displays will appear as indicated.
The following error messages may appear when inputting a program. Correct
the error as indicated and continue with the input operation. The asterisks in
the displays shown below will be replaced with numeric data, normally an
address, in the actual display.
Cause and correction
Address
Instruction
0200
LD
0201
TIM
#
0202
TIMH(15)
#
Section 4-6
Operands
0002
00
0123
01
0500