GPO and Distance

8
GPO and all electrical wiring must comply with AS/NZS 3000.
Ensure service cord is properly secured and protected from mechanical damage.

Ducts and Fittings

4 Star units install the thermistor into the discharge air duct between two &
three metres from the oulet of the unit. Air inlet and outlet on external units
can be changed to opposite side to suit installation needs.
If the inlet/outlet configuration is changed it may be necessary to also swap the
outlet position for the combustion fan. See instruction in section 9.
NOTE: 4 Star units also have an internal cover on the
heat exchanger side which must also be removed &
fitted to other side if the covers are being
45
External Installation
External Installation
Part 5442225 issue E