Zones Setup (cont)

Navigator 1 Thermostat Installer Parameters

Parameter
Temperature Display Zone
Temperature
Measurement
Common Zone
Temperature
Measurement
Switched Zones

Navigator 2 Thermostat Installer Parameters

Parameter
Temperature Display Zone
Temperature
Measurement
Common Zone
Temperature
Measurement
Switched Zones
NOTE: There is no difference in setup between a wall mounted wired and wireless
remote Navigator installation.
LTIPLE CONTROLLERS – INDIVIDUAL ZONES (Example)
MULTIPLE CONTROLLERS – INDIVIDUAL ZONES (Example)
This feature allows each controller on the navigator system to be assigned to a zone
or a group of zones that is not assigned to any other controller on the system. In this
configuration, there is no interaction between controllers. Each has complete
independent control over its zones and the program set on that control is unique to
that controller and zone. In this mode, you will NOT assign any controller to the
common or unswitched zone.
To enable this feature, Multiple Controllers in individual zones, the system
configuration parameter must be set to 3 (Individual) on all controllers. Best results
will be achieved when one Navigator controller is assigned to zones 1 & 2, the other
to zones 3 & 4. The common zone must be disabled. This assumes that the
Navigators are physically installed in Zones 1 and 3 respectively.

Navigator 1 Controller Installer Parameters

Parameter
Unswitched Zone
Switched Zones
Temperature Display Zone
Temperature
Measurement
Common Zone
Temperature
Measurement
Switched Zones
Navigator 2 Controller Installer Parameters
Parameter
Unswitched Zone
Switched Zones
Temperature Display Zone
Temperature
Measurement
Common Zone
Temperature
Measurement
Switched Zones
Id
Value
Meaning
3
1
Displaying temperature in zone 1
4
0
No measurement from common zone
5
3
Measuring zones 1 & 2
Id
Value
Meaning
3
3
Displaying temperature in zone 3
4
0
No measurement from common zone
5
12
Measuring zones 3 & 4
Id
Value
Meaning
1
0
Common zone disabled
2
3
Controlling Zones 1 & 2
3
1
Displaying temperature in zone 1
4
0
No measurement from common zone
5
3
Measuring zones 1 & 2
Id
Value
Meaning
1
0
Common zone disabled
2
12
Controlling Zones 3 & 4
3
3
Displaying temperature in zone 3
4
0
No measurement from common zone
5
12
Measuring zones 3 & 4