Flue Installation
All flue materials not supplied with this product and used in its installation must be
AGA approved.
This heater must be flued using Ø100mm (minimum) metal flue pipe.
Any flue pipe sections which are not accessible for inspection shall be twin walled
or stainless steel.
Total flue length shall not exceed 6 metres and have no more than two 90 bends.
All flue pipe connections and joins must be sealed with approved materials to
comply with AS/NZS 5601.
All flue configurations must comply withAS/NZS 5601 and local building codes.
8
Wall Cover Plate
38
Under Floor Installation
Under Floor Installation