CHAPTER 3 PRIMEPOWER200 Rackmount (4U) Server
General installation notes
32
– Be careful of injuries during installation of the PRIMEPOWER200 Rackmount (4U)
Server into the rack.
– Do not install the PRIMEPOWER200 Rackmount (4U) Server into a rack if the server unit
may make the entire rack unstable.
– Maximum configured weight of this unit: 50 kg (110.38 lb.)
 If the PRIMEPOWER200 Rackmount (4U) Server is supplied with power from a power strip or
service outlet of other units, it may overload the power supply cord or the power strip of other
units.
– Confirm that the current rating of the power strip or service outlet exceeds the combined
ratings of all equipment it is supplying.
– Electrical ratings of this unit: 100 to 240VAC, 6.1A to 2.6A, 50/60Hz, single-phase
 Reliable earthing of rack-mounted equipment should be maintained. Particular attention should
be given to non-direct-to-mains connections (e.g. via power strips, etc.).
Connect the ground before connecting any of the power supply
CAUTION
lines. If all of the power cables are connected to a single power
strip, high leakage current exceeding the stipulated value may leak
through to the earth lead of the power strip.
If the power strip is not directly connected to the main distribution
panel, use a power strip with an industrial plug.
 Do not block the ventilation holes.
 Do not install the PRIMEPOWER200 Rackmount (4U) Server where it will be exposed to
sunlight or sources of heat.
 Do not install the PRIMEPOWER200 Rackmount (4U) Server in dusty places or places where
it will be exposed to corrosive gases or sea breezes.
 Keep the PRIMEPOWER200 Rackmount (4U) Server isolated from vibration. Install the
PRIMEPOWER200 Rackmount (4U) Server on a level surface so that it does not tilt.
 Make sure that the AC power supply source is grounded properly using a maximum resistance
of 100 Ohms. Also, do not ground the AC power supply source using a shared ground. Use
only an independent grounding point. Otherwise, the PRIMEPOWER200 Rackmount (4U)
Server may malfunction.
 Do not run a cable under a unit or allow a cable to become taut. Do not disconnect the power
cable when the power is on.
 Do not place anything on the PRIMEPOWER200 Rackmount (4U) Server. Do not use the top
of the PRIMEPOWER200 Rackmount (4U) Server as a workspace.
 To prevent condensation in the PRIMEPOWER200 Rackmount (4U) Server, do not raise the
ambient room temperature rapidly in winter.
Use the PRIMEPOWER200 Rackmount (4U) Server only after it has warmed up sufficiently.
 Do not install the PRIMEPOWER200 Rackmount (4U) Server near EM noise generating
devices such as photocopiers, air conditioners, or welders.