4.
Battery Type
To ensure the batteries are receiving the proper charge voltage, the Battery
Type must be selected for the type of batteries used in the system: GEL Cell,
Liquid Lead Acid and AGM. The default setting is GEL Cell.
This voltage varies depending on the batteries used, as specified below.
BATTERY TYPE
GEL Cell
Liquid Led Acid
AGM
5.
Charge Rate
The battery charger's maximum output current can be specified using the
Charge Rate menu. The default is 100% of the maximum charge rate. Refer to
the inverter/charger Operator's manual for specific system settings.
Charge Rate:
Charge Rate:
100% of max
90%
1 999 Trace Engineering
ã
BULK V DC
FLOAT V DC
14.1 V dc
13.6 V dc
14.6 V dc
13.4 V dc
14.4 V dc
13.4 V dc
Battery Type:
Battery Type:
GEL Cell
Liquid Lead Acid
Figure 16
Battery Type Selections
Charge Rate:
• • • •
80%
Figure 17
Charge Rate Selections
RC7 & RC7GS Remote Controls
EQUALIZE V DC
Defeated
15.5 V dc
15.5 V dc
Battery Type:
AGM
Charge Rate:
Charge Rate:
20%
10%