Table 3.1 Button Function In Configuration Mode - Newport i8-AL Operator's Manual

I series temperature/process limit alarm controller
Table of Contents

Advertisement

3.1 Introduction (continued)

Table 3.1 Button Function in Configuration Mode

• To enter the Menu, the user must first press a button.
• Use this button to advance/navigate to the next menu item.
The user can navigate through all the top level menus by
a
pressing a .
(MENU)
• While a parameter is being modified, press a to escape
without saving the parameter.
• Press the up b button to scroll through "flashing" selections.
When a numerical value is displayed press this key to increase
value of a parameter that is currently being modified.
b
• Holding the b button down for approximately 3 seconds will
(UP)
speed up the rate at which the set point value increments.
• In the Run Mode press b causes the display to flash the PEAK
value – press again to return to the Run Mode.
• Press the down c button to go back to a previous Top Level
Menu item.
• Press this button twice to reset the device to the Run Mode.
• When a numerical value is flashing (except set point value) press c
to scroll digits from left to right allowing the user to select the desired
digit to modify.
c
• When a setpoint value is displayed press c to decrease value of a
(DOWN)
setpoint that is currently being modified. Holding the c button
down for approximately 3 seconds will speed up the rate at which
the setpoint value is decremented.
• In the Run Mode press c causes the display to flash the VALLEY
value – press again to return to the Run Mode.
• Press the enter d button to access the submenus from a Top Level
Menu item.
• Press d to store a submenu selection or after entering a value —
d
the display will flash a STRD message to confirm your selection.
(ENTER)
• To reset flashing Peak or Valley press d.
• In the Run Mode, press d twice to enable Standby Mode with
flashing STBY .
Reset: Except for Alarms, modifying any settings of the menu
configuration will reset the device prior to resuming Run Mode.