Wiring the Regulator Board Terminal Strip
Table 7.8 - Wiring Signal and Control I/O to the Terminal Strip (Continued)
Description
Wiring the Output Status Relays
Parameters/Wiring Connections
Both Form A and Form B contacts are rated for
250 VAC/30 VDC at 5 amps resistive or 2 amps inductive
load.
The following parameter must be set:
P.013: Output Relay Configuration
Note that depending on the setting of parameter P.013, the
relay coil will energize (the normally-open contact will close
and the normally-closed contact will open). Refer to the
GV3000/SE Software Start-Up and Reference manual for
more information.
Parameter P.013 selects output indication.
N.O.
N.C.
Com
Com.
28 29 30 31
User-Supplied
Device
7-17